What Open & Closed States Mean In AVTECH Switch Sensors

The list below shows the conditions that correspond to OPEN and CLOSED for each of AVTECH’s switch sensors.

Air Flow 1 Sensor (NC) RMA-AF1-SEN

CLOSED (Normal) Air is NOT flowing through the sensor. The flap is closed.

OPEN (Alarm) Air is flowing through the sensor. The flap is open.

Air Flow 2 Sensor (NO) RMA-AF2-SEN

CLOSED (Alarm) Air is flowing through the sensor. The flap is open.

OPEN (Normal) Air is NOT flowing through the sensor. The flap is closed.

Flood Sensor Spot RMA-FS2-SEN

CLOSED (Normal) Water is NOT detected.

OPEN (Alarm) Water is detected.

Flood Sensor w/ Cable (8′, 24′) RMA-F008-SEN, RMA-F024-SEN

Flood Detection Switch

CLOSED (Normal) Water is NOT detected.

OPEN (Alarm) WATER is detected.

Cable Fault Detection Switch

CLOSED (Normal) No cable fault

OPEN (Alarm) Cable fault

Fuel Tank Level Sensor (NC) RMA-FTL1-SEN

CLOSED (Normal) The water level has fallen. The float switch face is down.

OPEN (Alarm) The water level has risen. The float switch face is up.

Fuel Tank Level Sensor (NO) RMA-FTL2-SEN

CLOSED (Alarm) The water level has risen. The float switch face is up.

OPEN (Normal) The water level has fallen. The float switch face is down.

Mini UPS & Power Sensor RMA-MUPS-SEN

CLOSED (Normal) Main power is on.

OPEN (Alarm) Main power is off.

Motion Sensor RMA-MOT2-SEN

CLOSED (Normal) Motion is NOT detected.

OPEN (Alarm) Motion is detected.

Panic Button 1 RMA-PB1-SEN

CLOSED (Alarm) The button is down (pressed).

OPEN (Normal) The button is up (NOT pressed).

Panic Button 2 RMA-PB2-SEN

CLOSED (Alarm) The button is down (pressed).

OPEN (Normal) The button is up (NOT pressed).

Power Sensor RMA-PS1-SEN

CLOSED (Normal) The power source is on.

OPEN (Alarm) The power source is off.

Room Entry Sensor RMA-RE1-SEN

CLOSED (Normal) The door is closed. The magnet and proximity sensor are together.

OPEN (Alarm) The door is open. The magnet and proximity sensor are apart.

Smoke Sensor w/ Escape Light RMA-SS1-SEN

CLOSED (Alarm) The smoke alarm is on.

OPEN (Normal) The smoke alarm is off.

Sound, Light & Entry Sensor RMA-SLE-SEN

General (Switch 1)

CLOSED (Alarm) At least one of the other switches (2, 3 or 4) is closed. At least one condition (sound, light or entry) is detected.

OPEN (Normal) All other switches (2, 3 and 4) are open. NO sound, light or entry is detected.

Sound (Switch 2)

CLOSED (Alarm) Sound is detected.

OPEN (Normal) Sound is NOT detected.

Light (Switch 3)

CLOSED (Alarm) Light is detected.

OPEN (Normal) Light is NOT detected.

Entry (Switch 4)

CLOSED (Alarm) The door is open. The magnet and proximity sensor are apart.

OPEN (Normal) The door is closed. The magnet and proximity sensor are together.

Water Tank Level Sensor (NC) RMA-WTL1-SEN

CLOSED (Normal) The water level has fallen. The float switch face is down.

OPEN (Alarm) The water level has risen. The float switch face is up.

Water Tank Level Sensor (NO) RMA-WTL2-SEN

CLOSED (Alarm) The water level has risen. The float switch face is up.

OPEN (Normal) The water level has fallen. The float switch face is down

Facebooktwitterredditpinterestlinkedinmail
Room Alert is Made in the USA, ships worldwide from our locations in the US and EU, and has been protecting facilities since 1988.

You may find Windows Command Prompt at the following path:

  • Windows 7 & 8
    Start--> All Programs--> Accessories--> Command Prompt
  • Windows 10
    Start--> All Apps--> Windows System--> Command Prompt

To run Windows Command Prompt as an administrator:

  • Windows 7 & 8
    Right-click on Command Prompt and select Run as administrator.
  • Windows 10
    Right-click on Command Prompt, select More and then select Run as administrator.

Example Polling Method Properties saved in Orion SolarWinds:

If you are using this client, you should configure the general SNMPv3 Credentials, but leave the Read / Write SNMPv3 Credentials section blank.

Room Alert Link- Supported Firmware Updates



Current S modelsCurrent E models
Room Alert 32SRoom Alert 32E
Room Alert 12SRoom Alert 12E
Room Alert 4E
Room Alert 3E

Room Alert Manager - Compatible Devices

The latest version of Room Alert Manager supports only the devices below.

It does not support any legacy Room Alert or TemPageR models.

Current S modelsCurrent E models
Room Alert 32SRoom Alert 32E
Room Alert 12SRoom Alert 12E
Room Alert 3SRoom Alert 4E
Room Alert 3E
Room Alert 3W