Support

Knowledge Base  /  Frequently Asked Questions  /  Room Alert

How To Reset A Room Alert Monitor To Factory Defaults

Using an older version of the Room Alert Monitor web interface? Please click here for the appropriate FAQ.

You may reset your Room Alert Monitor to factory defaults in 3 ways:

– Through Room Alert Monitor’s web interface

– With the physical reset button on the Room Alert unit

– Through Room Alert’s Telnet menu *

  * Not available on the Room Alert 3 Wi-Fi or Room Alert ‘S’ models.

When you reset your Room Alert Monitor to factory defaults, the unit loses all of the settings previously configured, such as alarm thresholds and static IP addresses, but retains firmware updates.

Reset A Room Alert 32S, 12S, 3S, 32E/W, 12E, 4E, or 3E

Select one of the tabs below to reset your Room Alert Monitor to defaults.

Through its web interfaceUsing its physical reset buttonThrough its Telnet menu

1. Open your Room Alert Monitor’s web interface. This FAQ has instructions: How To Open Your Room Alert Monitor’s Built-in Web Interface.

2. Select Settings in the navigation bar to the left.

3. Then select Advanced from the options below Settings.

Navigation Bar -- Settings--Advanced

4. Select Reset to Defaults in the upper right corner of the screen.

  • On Room Alert ‘S’ models, this button is located toward the bottom of the screen.

Reset To Defaults Button

5. Select Yes in the Confirm Reset dialog box.

Reset_RA_Confirm

6. Your unit will reboot with factory settings restored.

The reset button is recessed behind a small hole in the unit’s enclosure. You can reach it with a paperclip or other small tool. Click below to view the location of your device’s button:

Room Alert 32S & 32E/W

Room Alert 12S & 12E

Room Alert 4E

Room Alert 3E & 3S

To reset the unit with the physical reset button:

1. With your Room Alert Monitor connected to Ethernet and power, press and hold the reset button for at least 10 seconds until the left ‘link’ LED on the network jack turns off momentarily and then turns on again.

For the Room Alert 32E, you may wish to observe the status LEDs on the front rather than the network jack LED. When you initiate a reset, the status LEDs will first turn red, then cycle through red and green, and finally return to their original state.

2. Your unit will reboot with factory settings restored.

* Not available on Room Alert ‘S’ models.

If you don’t have access to reset the Room Alert Monitor through its web interface or with its physical reset button, you can reset the unit through its Telnet menu.

You must have Telnet enabled on your Windows system in order to complete the steps below. Telnet is disabled by default in Windows versions Vista and above. Please see our FAQ How To Enable Telnet In Windows (Versions Vista And Above) for help.

1. Open Windows Command Prompt, which you may find at the following path on your Windows system: Start–> All Programs–> Accessories–> Command Prompt.

2. At the prompt, enter the following command, as shown in the example below.

telnet <Room Alert Monitor IP address> 9999

telenet_command_9999

3. If you are prompted for your Room Alert Monitor password, enter it and then press the Enter key on your keyboard. Otherwise, simply press Enter.

telnet_Password_Prompt

You must press Enter within a few seconds or you’ll get a ‘Connection to host lost’ message. If you see that message, press Enter to get the prompt back and re-enter the telnet command from Step 2.

4. The Telnet menu will appear as shown below.

5. At the Your choice? prompt, enter 7, which corresponds to ‘factory defaults.’

telnet_Your_choice_7

6. Enter Y when the confirmation message appears. You’ll then see a message that the unit is resetting.

telnet_Reset_Confirm_Msg

7. Then, the Telnet menu will reappear. At the Your choice? prompt, enter 9, which corresponds to ‘save and exit.’

8. Your Room Alert Monitor will reboot with factory settings restored.

After the unit reboots, it attempts to obtain an IP address using DHCP. You can find instructions to discover your Room Alert Monitor again in our FAQ, How To Discover A Room Alert Monitor.

Reset A Room Alert 3 Wi-Fi

Select one of the tabs below to reset your Room Alert 3 Wi-Fi to defaults.

Through its web interfaceUsing its physical reset button

1. Open your Room Alert Monitor’s web interface. You may open the interface using Device Discovery, Device ManageR, or your account at RoomAlert.com. You may also type the IP address of the unit directly into the address bar of your web browser.

2. Select Alert Options in the navigation bar at the top of the page.

3. Then select Advanced from the options below Alert Options.

4. Select Reset to Defaults in the upper right corner of the screen.

5. Select Yes in the Confirm Reset dialog box.

Reset_RA_Confirm

6. Your unit will reboot with factory settings restored.

The reset button is recessed behind a small hole in the unit’s enclosure. You can reach it with a paperclip or other small tool. Click below to view the location of your device’s button:

Room Alert 3W

To reset the unit with the physical reset button:

1. With your Room Alert 3 Wi-Fi connected to power, press and hold the reset button for at least 10 seconds.

2. Your unit will reboot with factory settings restored.

After you reset the Room Alert 3 Wi-Fi, the unit needs to be manually connected to your Wireless network again. For instructions please see, How To Set Up Room Alert 3 Wi-Fi (VIDEO).

Facebooktwitterredditpinterestlinkedinmail
Room Alert is Made in the USA, ships worldwide from our locations in the US and EU, and has been protecting facilities since 1988.

You may find Windows Command Prompt at the following path:

  • Windows 7 & 8
    Start--> All Programs--> Accessories--> Command Prompt
  • Windows 10
    Start--> All Apps--> Windows System--> Command Prompt

To run Windows Command Prompt as an administrator:

  • Windows 7 & 8
    Right-click on Command Prompt and select Run as administrator.
  • Windows 10
    Right-click on Command Prompt, select More and then select Run as administrator.

Example Polling Method Properties saved in Orion SolarWinds:

If you are using this client, you should configure the general SNMPv3 Credentials, but leave the Read / Write SNMPv3 Credentials section blank.

Room Alert Link- Supported Firmware Updates



Current S modelsCurrent E models
Room Alert 32SRoom Alert 32E
Room Alert 12SRoom Alert 12E
Room Alert 4E
Room Alert 3E

Room Alert Manager - Compatible Devices

The latest version of Room Alert Manager supports only the devices below.

It does not support any legacy Room Alert or TemPageR models.

Current S modelsCurrent E models
Room Alert 32SRoom Alert 32E
Room Alert 12SRoom Alert 12E
Room Alert 3SRoom Alert 4E
Room Alert 3E
Room Alert 3W

RA32W_Reset

Located on back of unit, between the switch sensor ports and power port.

RA12E_Reset

Located on back of unit, next to the LTA port.

ø;

Located on back of unit, next to the custom relay / light tower port.

RA3E_Reset

Located on back of unit, below the vents and next to the switch port.

RA3W_Reset

Located on back of unit, below the vents and next to the switch port.