How To Set Up Alerts For Your Digital Active Power Sensor In Device ManageR

For information on installing your Digital Active Power Sensor on a power cord, please see the Digital Active Power Installation Note.

To configure alerts in Device ManageR for the Digital Active Power Sensor, please perform Step 1 and Step 2 as shown below:

Step 1: Set up your Digital Active Power Sensor in your Room Alert Monitor's web interface.

Your Room Alert Monitor must be on at least the minimum firmware version below to be compatible with the Digital Active Power Sensor. 

  • Room Alert 32E v3.1.0
  • Room Alert 12E v3.1.0
  • Room Alert 4E v4.1.0
  • Room Alert 3E v2.1.0
  • Room Alert 3 Wi-Fi v2.0.0

You may download the latest firmware from your account at RoomAlert.com.

Before you can set up Digital Active Power sensor alerts in Device ManageR, you must first configure the sensor in your Room Alert Monitor. Your Digital Active Power Sensor will not appear in Device ManageR unless you first configure it in your Room Alert Monitor.

To configure your Digital Active Power Sensor, follow these steps:

1. Open your Room Alert Monitor’s web interface. You may open the interface using Device Discovery, Device ManageR, or your account at RoomAlert.com. You may also type the IP address of the unit directly into the address bar of your web browser.

2. Navigate to SettingsNetwork in the navigation bar to the left.

3. Find the digital sensor interface that matches the port you connected your Digital Active Power Sensor to. For example, if you used the first digital port on your Room Alert Monitor, look for Sensor 1 Alarm Configuration; if you used the second, look for Sensor 2 Alarm Configuration, and so on.

4. In the Sensor Type drop-down menu, select Temp/Active Power.

5. In Sensor Label, you may leave the default, Ext Sensor X, or name your Digital Active Power Sensor. In our example, we’re calling it DAP Server 1.

6. In Power, make a selection in the drop-down menu depending on how you intend to alert:

– If you wish alerts to come only from Device ManageR, leave the default Alert Disabled. This means the Room Alert itself will not go into an alert state for the Power portion of the Digital Active Power Sensor.

– If you wish also to alert from the Room Alert unit itself, select No Power Detected or Power Detected.

7. Select Save Settings at the top or bottom of the page. Your Room Alert Monitor will automatically reboot and commit your changes.

Step 2: Set up your Digital Active Power Sensor alerts in Device ManageR.

Your Device ManageR software must be at the minimum version of 6.3.5 to be compatible with the Digital Active Power Sensor. You may download the latest version of Device ManageR from your account at RoomAlert.com.

For a detailed walk-through of setting up alerts in Device ManageR, please review our FAQ, How To Create Alerts In Device ManageR: Start To Finish

Once you have configured your mail server, your contacts, your actions and your Action/Notification Lists in Device ManageR , you may set up an alert for your Digital Active Power Sensor by following the instructions below:

1. Open Device ManageR in your web browser. You may open it by entering ‘localhost:8080’ or ‘<IP address of Device ManageR’s host system>:8080’ in your browser’s address bar.

2. Select Alerts / Tasks in the navigation bar to the left.

3. In the Alerts / Tasks menu, select Alerts.

4. Select Add to add a new alert.

5. In the Add New Alert screen that appears:

– In Name, enter a name for your alert. Our example is called DAP Server 1 – No Power Detected.

– In Device, select your Room Alert Monitor from the drop-down list. We’re choosing the Room Alert 32E in our data center.

– In Alarm when…, you’ll then see a drop-down list with all of the unit’s individual sensors. Select your Digital Active Power Sensor – Volts. (Ext Sensor 1 – Volts, for example.)

– In is, set the threshold for the Digital Active Power Sensor:

To alert for power OFF, enter ‘less than (<) 0.18.’

The Digital Active Power Sensor considers power to be off when it detects less than 0.18 volts.

With this setting, when the voltage reaches 0.17 or lower, Device ManageR will go into an alert state; this alert state will clear when the voltage reaches 0.18 or higher.

To alert for power ON, enter ‘greater than or equal to (>=) 0.18.’

The Digital Active Power Sensor considers power to be on when it detects 0.18 or more volts.

With this setting, when the voltage reaches 0.18 or higher, Device ManageR will go into an alert state; this alert state will clear when the voltage reaches 0.17 or lower.

– In Alarm if item is unavailable for X scans, you may leave the default, 4 scans, or enter another value. You may also disable this feature if you wish by unchecking the check box. In our example, we’re leaving the default.

– In Action / Notification List, select an already-configured list from the drop-down menu or create a new one by selecting Add. Here we’re choosing a List we called Notify IT Staff.

– Then select Save.

 

Facebooktwitterredditpinterestlinkedinmail
Room Alert is Made in the USA, ships worldwide from our locations in the US and EU, and has been protecting facilities since 1988.

You may find Windows Command Prompt at the following path:

  • Windows 7 & 8
    Start--> All Programs--> Accessories--> Command Prompt
  • Windows 10
    Start--> All Apps--> Windows System--> Command Prompt

To run Windows Command Prompt as an administrator:

  • Windows 7 & 8
    Right-click on Command Prompt and select Run as administrator.
  • Windows 10
    Right-click on Command Prompt, select More and then select Run as administrator.

Example Polling Method Properties saved in Orion SolarWinds:

If you are using this client, you should configure the general SNMPv3 Credentials, but leave the Read / Write SNMPv3 Credentials section blank.

Room Alert Link- Supported Firmware Updates



Current S modelsCurrent E models
Room Alert 32SRoom Alert 32E
Room Alert 12SRoom Alert 12E
Room Alert 4E
Room Alert 3E

Room Alert Manager - Compatible Devices

The latest version of Room Alert Manager supports only the devices below.

It does not support any legacy Room Alert or TemPageR models.

Current S modelsCurrent E models
Room Alert 32SRoom Alert 32E
Room Alert 12SRoom Alert 12E
Room Alert 3SRoom Alert 4E
Room Alert 3E
Room Alert 3W