How To Troubleshoot Sensor Data Loading Issues On The Status Screen Of A Room Alert Monitor

Room Alert Monitors load the sensor data for display on the Status page using a background XML HTTP request for JSON data.

If sensor data is not loading in the Status page, first verify that you can access the JSON data in your web browser.

  • For current & legacy ‘E’ models, enter http://<IP Address of Device>/getData.json in your web browser address bar.
  • For Room Alert ‘S’ models, enter http://<IP Address of Device>/status.json in your web browser address bar.
    • If your Room Alert ‘S’ model is configured to use HTTPS, enter https://<IP Address of Device>/status.json instead.

You should see output similar to the following:

getData_JSON (2)

If the data fails to load, the cause can usually be traced to a proxy server or Microsoft ISA server.

  • If your network has a proxy server or Microsoft ISA server, be sure that it is configured to ignore requests to and from the Room Alert Monitor.
  • Also verify that you do not have any local Internet security, anti-virus, or firewall applications that may be blocking, filtering or caching the background requests to this page.

Older Room Alert models

You may also test older units by entering in http://<IP Address of Device>/mobile.txt in your browser’s address bar.

You should see output like the following:

mobiletxt (2)

Please note that current firmware for the Room Alert 32S, 12S, 32E/W, 12E, 4E and 3E does not support the mobile.txt feature.

If you see an image loading like the one above, your issue is related to either a web browser, security device/application or anti-virus program blocking requests and traffic made to the unit. You will want to further examine your current security settings on your security applications and devices running on your PC and on your network.

Facebooktwitterredditpinterestlinkedinmail
Room Alert is Made in the USA, ships worldwide from our locations in the US and EU, and has been protecting facilities since 1988.

You may find Windows Command Prompt at the following path:

  • Windows 7 & 8
    Start--> All Programs--> Accessories--> Command Prompt
  • Windows 10
    Start--> All Apps--> Windows System--> Command Prompt

To run Windows Command Prompt as an administrator:

  • Windows 7 & 8
    Right-click on Command Prompt and select Run as administrator.
  • Windows 10
    Right-click on Command Prompt, select More and then select Run as administrator.

Example Polling Method Properties saved in Orion SolarWinds:

If you are using this client, you should configure the general SNMPv3 Credentials, but leave the Read / Write SNMPv3 Credentials section blank.

Room Alert Link- Supported Firmware Updates



Current S modelsCurrent E models
Room Alert 32SRoom Alert 32E
Room Alert 12SRoom Alert 12E
Room Alert 4E
Room Alert 3E

Room Alert Manager - Compatible Devices

The latest version of Room Alert Manager supports only the devices below.

It does not support any legacy Room Alert or TemPageR models.

Current S modelsCurrent E models
Room Alert 32SRoom Alert 32E
Room Alert 12SRoom Alert 12E
Room Alert 3SRoom Alert 4E
Room Alert 3E
Room Alert 3W

Current & Legacy Room Alert "E" Models

Current ModelsLegacy Models
Room Alert 32ERoom Alert 32W
Room Alert 12ERoom Alert 26W
Room Alert 4ERoom Alert 24E
Room Alert 3ERoom Alert 11E
Room Alert 7E
TemPageR 4E
TemPageR 3E